Checked against primary sources 2026-08-24
The space in front and the space above are two different rules
Most candidates can quote one depth figure and miss everything else in the section. The marks sit in the conditions, in the entrance rules, and in the zone above the equipment that is not working space at all.
On this page
- What the section asks for before it asks for a number
- Where depth is measured from, and why the number moves
- The two dimensions nobody looks up
- Getting in and out, and the two ratings that change the answer
- The zone above the equipment is not working space
- Illumination, and the detail inside it
- Answering one of these under a clock
- What this page cites
What the section asks for before it asks for a number
Working space, and the access to and egress from it, has to be provided and maintained about all electrical equipment so the equipment can be operated and maintained safely (NEC 110.26).
The dimensions in 110.26(A) attach to equipment likely to require examination, adjustment, servicing or maintenance while energized. That qualifier does real work. A stem that describes the equipment carefully is often telling you whether the dimensions apply at all before it asks you for one.
Depth, width and height are three separate requirements and an installation satisfies all three or it fails. Generous width does not buy back short depth.
Where depth is measured from, and why the number moves
Distances are measured from the live parts where the live parts are exposed, and from the enclosure front or the opening where the live parts are enclosed (NEC 110.26(A)(1)). On a dead-front panelboard that means the front of the can, not the bus behind it, and getting it backwards costs you the depth of the enclosure.
The figure itself lives in Table 110.26(A)(1), indexed by nominal voltage to ground one way and by one of three conditions the other. Look it up. There is more than one number in it, which is the whole reason candidates who answer from memory lose these items.
The conditions are decided by what sits on the other side of the space, and they are prose, not arithmetic.
- Condition 1. Exposed live parts on one side of the working space and nothing live or grounded on the other, or exposed live parts on both sides where they are effectively guarded by insulating material.
- Condition 2. Exposed live parts on one side and grounded parts on the other. Concrete, brick and tile walls count as grounded parts.
- Condition 3. Exposed live parts on both sides of the working space, with no effective guarding between them.
Read the guarding clause in Condition 1 twice, because live parts on both sides is not automatically Condition 3. Effective guarding by insulating material puts the same physical arrangement back into Condition 1, and an item that mentions an insulating barrier is testing precisely that.
There is also a permission most people have never read. Where equipment in an existing building is being replaced, Condition 2 clearance is allowed between dead-front assemblies sitting across an aisle from each other, provided written procedures stop both sides being opened at the same time and the people servicing it are qualified and authorized (NEC 110.26(A)(1)(c)).
And the section does not ask for working space behind or beside a dead-front assembly where every connection and every renewable or adjustable part can be reached from somewhere else. Where rear access is needed to get at nonelectrical parts, 30 inches of horizontal space is what it asks for instead (NEC 110.26(A)(1)(a)).
The two dimensions nobody looks up
Width is the width of the equipment or 30 inches, whichever is greater, measured across the face rather than in front of the one breaker in the stem (NEC 110.26(A)(2)). Equipment doors and hinged panels have to swing at least 90 degrees.
Height is clear space from the grade, floor or platform up to 6½ feet or the height of the equipment, whichever is greater (NEC 110.26(A)(3)). A duct run at 6 feet across the front of a panel is a violation of a dimension almost nobody checks.
The working space may not be used for storage (NEC 110.26(B)).
That last one is what catches a finished building. A clear space in a bare mechanical room does not stay clear once somebody needs a home for a ladder, and an item describing what else is in the room is usually planting exactly that.
Two more subsections are worth knowing exist. 110.26(A)(4) sets separate terms for equipment installed where access is limited, such as above a suspended ceiling. 110.26(A)(5) deals with equipment at 1000 volts ac or 1500 volts dc and below sharing a vault, room or enclosure with exposed parts operating above those voltages, which have to be separated off by a partition, fence or screen.
Getting in and out, and the two ratings that change the answer
Two amperage thresholds live in 110.26(C) and they do completely different jobs. Items on this subject routinely hand you the wrong one and see whether you notice.
Large equipment gets an entrance to and egress from the working space at each end, not less than 24 inches wide and 6½ feet high (NEC 110.26(C)(2)). Large equipment there is defined two ways: equipment rated 1200 amperes or more that is also over 6 feet wide, or a set of service disconnecting means, or building or structure feeder disconnects, whose combined rating reaches 1200 amperes and whose combined width is over 6 feet.
That second limb is the trap, because no single enclosure in the lineup has to be 1200 amperes. Six 400 ampere service disconnects standing side by side are added together, for rating and for width, and the group can land inside the rule while every piece of it looks small.
Note the conjunction on the first limb as well. Both halves have to be true. A 1200 ampere motor control center that is 5 feet wide is not large equipment for this purpose.
Two exceptions bring it back to one entrance, one turning on unobstructed egress and one on doubling the working space depth. Read them in your own book rather than trying to remember which is which.
The door rule is a different number and a different subject. Where equipment rated 800 amperes or more that contains overcurrent, switching or control devices is installed, and a personnel door intended for entrance to or egress from that working space sits less than 25 feet from the nearest edge of it, the door has to open at least 90 degrees in the direction of egress and carry listed panic hardware or listed fire exit hardware (NEC 110.26(C)(3)).
So 1200 amperes governs how many ways out there are, and 800 amperes governs how the door behaves. Neither number tells you anything about the other.
The zone above the equipment is not working space
110.26(E) reserves a different volume for a different reason, and confusing the two is the most productive mistake on this subject. The dedicated space is the footprint of the equipment, its own width and its own depth, running from the floor to 6 feet above the equipment or to the structural ceiling, whichever is lower.
Working space is in front of the equipment and exists so a person can stand there. Dedicated space is the column the equipment sits in and exists so somebody else’s pipe does not end up over your gear. Piping, ducts, leak protection apparatus and other equipment foreign to the electrical installation may not occupy that zone (NEC 110.26(E)).
Above the dedicated space the answer flips. Foreign systems are allowed up there where protection is installed against condensation, leaks and breaks. Sprinkler protection for the room is allowed. A suspended ceiling with removable panels is allowed inside the dedicated space itself, which is the clue that a dropped ceiling is not the structural ceiling the 6 feet is measured to.
Illumination, and the detail inside it
Working spaces about service equipment, switchboards, switchgear, panelboards and motor control centers installed indoors have to be lit, and the catch is that control of all the luminaires by automatic means is not permitted within the working space (NEC 110.26(D)).
An occupancy sensor as the only control fails. A wall switch you can reach passes. No dimension is attached to this one at all, which is exactly why it gets asked.
One more short subsection: an electrical equipment room or enclosure kept locked is still considered accessible to qualified persons (NEC 110.26(F)). A stem that mentions a locked electrical room is usually not describing a violation.
Answering one of these under a clock
- Decide whether the dimensions apply. They attach to equipment likely to be examined, adjusted, serviced or maintained while energized.
- Name which of the six answers the stem wants. Depth, width, height, entrance, illumination and the dedicated space are separate rules with separate numbers.
- For depth, settle the condition before you open the table. The condition comes from what is on the other side of the space, and the table is entered by condition and by voltage together.
- Check the stem for a second violation before you commit. These items are usually written with one loud problem and one quiet one, and the quiet one is often above the equipment rather than in front of it.
Put one tab where Table 110.26(A)(1) starts and a second on 110.26(E). The second tab earns more, because the dedicated space is the rule people go looking for and cannot find, and by the time they find it they have spent four minutes.
What this page cites
- NEC 110.26 Spaces about electrical equipment. The parent text covers working space and the access to and egress from it, and the dimensions in 110.26(A) attach to equipment likely to be examined, adjusted, serviced or maintained while energized. source
- NEC 110.26(A)(1) Depth of working space, the three conditions, and the sentence that settles where the distance is measured from: the live parts if exposed, the enclosure front or opening if enclosed. Also carries the dead-front allowance in (a), the low voltage special permission in (b), and the existing building aisle permission in (c). source
- NEC Table 110.26(A)(1) The depth figures themselves, by nominal voltage to ground and by condition. Named here and deliberately not printed. Open your own book and tab it. source
- NEC 110.26(C)(2) Entrance to and egress from working space for large equipment. The 2026 text sets the trigger two ways, one for a single piece of equipment rated 1200 amperes or more and over 6 feet wide, and one for a group of service or building feeder disconnects reaching those figures on combined rating and combined width. Verified against NFPA code-making panel 1 second revision 7662. source
- NEC 110.26(C)(3) Personnel doors. The trigger is 800 amperes and a door less than 25 feet from the nearest edge of the working space, and what it buys is a door that opens at least 90 degrees in the direction of egress with listed panic hardware or listed fire exit hardware. Verified against NFPA code-making panel 1 second revision 7663. source
- NEC 110.26(D) Illumination of working spaces indoors, and the bar on controlling all the luminaires by automatic means inside the working space. Verified against NFPA code-making panel 1 second revision 7670. source
- NEC 110.26(E) Dedicated equipment space. The width and depth of the equipment, floor to 6 feet above the equipment or to the structural ceiling, whichever is lower. Not revised for the 2026 edition, so the existing text carries. Foreign systems are barred inside the zone and allowed above it with protection against condensation, leaks and breaks. source
- NEC 110.26(A)(2) Width of working space, the width of the equipment or 30 inches whichever is greater, with equipment doors and hinged panels opening at least 90 degrees. source
- NEC 110.26(A)(3) Height of working space, clear from the grade, floor or platform to 6½ feet or the height of the equipment, whichever is greater. source
- 16 TAC 73.100 Texas adopts the 2026 edition on 1 September 2026, so from that date this is the 110.26 your paper is written against. source