Texas Electrician ExamTexas journeyman & master

Checked against primary sources 2026-08-24

The 3 percent figure is a note, and knowing that is worth a mark on its own

Items are written to catch a candidate who treats a recommendation as a rule, and other items are written to catch the candidate who has overlearned that and forgets the two articles where the limit is real.

On this page
  1. What the code actually says about it
  2. The two articles where the limit is real
  3. Why it gets tested anyway
  4. The formula, both versions
  5. Worked forward
  6. Worked backward, which is the harder direction
  7. The five ways this goes wrong
  8. How to hold it under a clock
  9. What this page cites

What the code actually says about it

The length in a voltage drop calculation is the round trip, not the distance on the drawing A supply feeds a load two hundred feet away. Current travels out on one conductor and back on the other, so the conductor length in the calculation is four hundred feet for a single phase circuit. Using the one way distance halves the answer and is the most common error on this type of question. Three phase circuits use a different multiplier for the same physical reason. supply load out back 200 ft 200 ft out + 200 ft back the conductor in the formula is 400 ft the tape measure says one number, the formula wants another
One way on the tape measure, two ways in the formula. This single mistake halves more answers than any other. Voltage drop is an Informational Note, at 210.19 for branch circuits and 215.4(A)(2) for feeders, not a requirement. Exams still ask it.

For an ordinary branch circuit or feeder, nothing enforceable. The 3 percent and 5 percent figures everyone quotes sit in informational notes, one attached to the branch circuit conductor rule in Article 210 and one attached to the feeder rule in Article 215.

Those notes describe a conductor sized so the drop at the farthest outlet stays within 3 percent, with the total across feeder and branch circuit staying within 5 percent, as providing reasonable efficiency of operation. That is a description of good practice, not a requirement, and the difference is stated by the code about its own text.

NEC 90.5 sorts everything in the book into mandatory rules, permissive rules and explanatory material, and puts informational notes in the third bucket, which is explicitly not enforceable as a requirement.

So an item that asks what the code requires for voltage drop on an ordinary branch circuit has an answer, and the answer is that the code sets no percentage. A percentage sitting in the options is there to be left alone.

The two articles where the limit is real

Both are outside general wiring, both are in Chapter 5 or 6 territory, and both are written as hard numbers.

Sensitive electronic equipment

NEC 647.4(D) sets 1.5 percent as the ceiling on any branch circuit and 2.5 percent on feeder and branch circuit combined. Article 647 covers separately derived systems used to supply sensitive electronic equipment, and the tight numbers are the reason the article exists.

Fire pumps

NEC 695.7 sets two limits under two different conditions. The voltage at the controller line terminals may not drop more than 15 percent below normal under motor starting conditions, and the voltage at the load terminals may not drop more than 5 percent below the motor voltage rating with the motor running at 115 percent of its full load current rating.

Note the shape of that second one. It is measured at 115 percent of full load, not at full load, which means the calculation you run is not the one the stem first appears to be asking for. That detail is the item.

Both articles are enforceable text. Neither is a note. A candidate who has learned "voltage drop is only a recommendation" as a slogan will answer a fire pump item wrongly, which is why the slogan needs both halves.

Why it gets tested anyway

Because it is real engineering. A conductor that satisfies every ampacity rule in the book can still deliver unusable voltage at the far end of a long run, and nothing in the ampacity calculation notices.

Motors are the usual case. Low voltage at start means more current, more heat, and a motor that can fail to come up to speed. That is a failure the derating calculation cannot see, because derating is about the conductor and this is about the load.

So the paper tests the arithmetic in a subject where the code declines to compel the outcome, and that is a perfectly coherent thing for it to do.

The formula, both versions

Voltage drop is current times the resistance of the path. The only thing the two versions disagree about is how much conductor the current sees.

Use the one-way length in both. The multiplier already carries the return path, and doubling the length and then multiplying by 2 as well is the commonest way this calculation goes wrong by a factor of two.

Resistance comes out of Chapter 9. Table 8 gives direct-current resistance in ohms per 1000 feet, separately for copper and aluminum and separately for solid and stranded, with coated and uncoated columns for copper. Table 9 gives alternating-current resistance and reactance for conductors in a raceway, and it is the one to use where the item mentions power factor or reactance.

Divide the per-1000-feet figure by 1000 to get ohms per foot, or keep it in thousands and divide the length by 1000. Either works. Mixing them is a factor of a thousand and you will notice.

Worked forward

Take a 240 volt single phase circuit carrying 30 amperes to a load 150 feet away on 10 AWG copper. Read the resistance for that conductor in Chapter 9, Table 8 and confirm the figure in your own book; for stranded uncoated copper it is 1.24 ohms per 1000 feet.

  1. Convert the resistance: 1.24 divided by 1000 gives 0.00124 ohms per foot.
  2. Apply the single phase form: 2 times 150 feet times 30 amperes times 0.00124.
  3. That is 11.16 volts.
  4. As a percentage, 11.16 divided by 240 is 4.65 percent.

A number that size is why the notes exist. Nothing in the code stops you installing that circuit, and no motor at the end of it will thank you.

Change nothing but the system and the arithmetic barely moves. The same current, the same distance and the same conductor on a three phase circuit gives 9.66 volts, because 1.732 has replaced the 2 and nothing else has changed. If your three phase answer comes out larger than your single phase answer on the same inputs, you have used the wrong multiplier.

Worked backward, which is the harder direction

Given a drop you are willing to accept, the question becomes what conductor delivers it. Rearrange rather than guess.

  1. Turn the allowed percentage into volts. On the circuit above, 3 percent of 240 volts is 7.2 volts.
  2. Solve the same formula for resistance: 7.2 divided by the product of 2, 150 feet and 30 amperes.
  3. That gives 0.0008 ohms per foot, which is 0.8 ohms per 1000 feet.
  4. Go to Chapter 9, Table 8 and take the first size in the right material column whose resistance is at or below that figure. Here it is 8 AWG, which clears it; 10 AWG does not.

Round toward less resistance, which means toward the larger conductor. A conductor that is one size too small fails the requirement you set yourself, and on this type of item the option list will contain that size on purpose.

One consequence worth carrying off this page: upsizing for voltage drop does not change the circuit rating, the overcurrent device or what the circuit may supply. It changes the wire and nothing else.

The five ways this goes wrong

The first three are one error wearing different clothes. Every one of them comes from not picturing the path the current takes before writing anything down.

How to hold it under a clock

Do not memorize a formula with letters in it. Remember the sentence: current times the resistance of the path, and the path is longer than the run.

From that you can rebuild the forward version, the backward version and both multipliers without needing to recall which letter stood for what. The letters are where people go wrong on a paper they are already behind on.

What this page cites

NEC and National Electrical Code are registered trademarks of the National Fire Protection Association.

Trojan Digital Marketing is an independent company. We are not affiliated with, endorsed by, or sponsored by NFPA, TDLR, PSI Services, or any licensing authority.

Bring your own current copy of the National Electrical Code. The Texas exam is open book.

All practice questions are original. They are not actual exam questions.

Built and maintained by Jeff Clerisier, Trojan Digital Marketing.