Checked against primary sources 2026-08-24
Motor calculations, and the one distinction that decides them
A motor question hands you two different currents. Using the wrong one for the wrong step is how most people lose these points, and the wrong answer always looks reasonable.
On this page
Two currents, and they are not interchangeable
Every motor problem involves two numbers that both describe current, and the code uses them for different jobs.
The first comes off a table in Article 430, selected by horsepower, voltage and phase. Call it the table current. The second is printed on the motor itself. Call it the nameplate current.
They are usually close. They are almost never equal. And the code is specific about which one belongs to which step (NEC 430.6).
- The table current sizes the conductors, the ampere ratings of switches, and the branch-circuit short-circuit and ground-fault protection. Those are the three things 430.6(A)(1) names, in that order.
- The nameplate current sizes the separate overload device (NEC 430.6(A)(2)).
One other place uses the nameplate, and it is the duty-cycle rule for a motor that is not continuous duty. Conductors for short-time, intermittent, periodic or varying duty come off a percentage of the nameplate current instead (NEC 430.22(E)). That is the exception people forget when they have learned the split as a slogan.
A question that gives you both numbers is testing whether you know which is which, and the distractor answers are built from the other current.
Where the nameplate wins the whole circuit
The table does not govern every motor, and the code says so in the same subsection that establishes it.
Motors built for low speeds, meaning under 1200 RPM, motors built for high torques, and multispeed motors are excluded from the table by the opening words of 430.6(A)(1). Those motors carry higher or speed-dependent full-load currents and the nameplate is what you use.
Two exceptions go further and hand the entire branch circuit to a marked current. One covers equipment with a shaded-pole or permanent-split-capacitor fan or blower motor marked with the motor type. The other covers a listed motor-operated appliance marked with both motor horsepower and full-load current. In each case the current marked on the equipment nameplate governs the conductors, the disconnect, the controller, the short-circuit device and the overload device together, not just one of them.
The 2026 edition tightened both. The fan and blower exception now also asks that the equipment nameplate marking be at least the current marked on the fan or blower motor itself, and the appliance exception now asks for both horsepower and full-load current on the appliance, where the 2023 text asked only for a motor type marking.
Why the code works this way
It looks arbitrary until you think about what each device is protecting against.
Overload protection is watching the motor. It cares what that specific motor actually draws, so it reads the nameplate.
Short-circuit and ground-fault protection is watching the circuit, and it has to survive the starting current every time the motor starts (NEC 430.52). Rather than make you chase a locked-rotor figure for every unit, the code sets a maximum by motor type and device type in a table and lets you work from the standardized table current.
Once you see that, you stop having to memorize which is which. Protecting the motor means nameplate. Protecting the wire means table. Then check whether the motor is one of the kinds the table does not cover.
The sequence
- Look up the full-load current in the Article 430 table using horsepower, voltage and phase (NEC 430.6(A)(1)). Check first that the motor is not low speed, high torque or multispeed, and that no equipment marking exception applies.
- Size the branch-circuit conductors at not less than 125 percent of that table current (NEC 430.22), then apply ambient and conduit-fill corrections from Article 310.
- Size the overload protection from the nameplate current (NEC 430.32).
- Size the branch-circuit short-circuit and ground-fault device from the percentage in the branch-device table, applied to the table current, then round up to the next standard rating (NEC 430.52).
- For a group, size the feeder conductor from the several-motors sum (NEC 430.24), taking 125 percent of the largest table current and 100 percent of the rest.
- Size the feeder protective device from the largest branch-circuit device in the group plus the full-load currents of the other motors, then round down (NEC 430.62).
Steps two and four both start from the table current and can be done in either order. Step three starts somewhere else entirely. Candidates who work straight down the list without noticing the source change get step three wrong every time.
The 125 percent is not the continuous-load rule
You already know a 125 percent rule from Article 210, the one for continuous loads. The motor rule looks identical and is not the same rule.
The Article 210 rule turns on whether the load runs for three hours or more. The motor rule turns on whether the application is continuous duty, which is a classification of the driven machine, not a stopwatch reading.
Any motor application is treated as continuous duty unless the thing it drives cannot run continuously under load. A conveyor that runs all shift and a hoist that runs in bursts are classified differently, and the hoist goes to the duty-cycle table, where the percentage is applied to the nameplate current and varies with both the duty classification and the time rating of the motor (NEC 430.22(E)).
So the duty-cycle case changes two things at once, the multiplier and the current it is applied to. Applying continuous-load reasoning to a motor gets the right number for the wrong reason on most questions and the wrong number on the ones that test duty cycle.
Rounding runs three different directions
Three rules in one problem all talk about standard ampere ratings and they do not agree, which is why this is a reliable place to lose a point.
- General conductor protection, 240.4(B): round up to the next standard size only when all three of its conditions are met, and one of them caps the result at 800 amperes.
- Motor branch-circuit short-circuit and ground-fault protection, 430.52(C)(1): where the value calculated from the table is not a standard rating, the next higher standard rating is the normal path.
- Motor feeder short-circuit and ground-fault protection, 430.62(A): this one is a ceiling. If the calculated value is not a standard rating you take the next size down, because the next-higher permission belongs to the branch circuit and does not reach the feeder.
Two of those say next higher and one says the opposite, and a candidate uses all three in the same question. Know which article and which part you are standing in before you round anything.
What to practice
Not the table values. You will have the book.
Practice the habit of writing both currents at the top of your scratch paper and labeling them before you start. Table current on the left, nameplate on the right. Then every step points at one of them.
Add one line above them: what kind of motor is this. If the answer is low speed, high torque, multispeed, or a marked appliance, the left column is empty and everything comes off the nameplate.
That habit is worth more on this section than any amount of memorization, because the arithmetic is easy and the sourcing is where the points go.
What this page cites
- NEC 430.6 Ampacity and rating determination. Read this before anything else in the article.
- NEC 430.6(A)(1) Table values govern conductor ampacity, switch current ratings and branch-circuit short-circuit and ground-fault protection, instead of the nameplate. Excludes motors built for low speeds under 1200 RPM, motors built for high torques, and multispeed motors. Exception No. 2 covers shaded-pole and permanent-split-capacitor fan and blower motors, Exception No. 3 listed motor-operated appliances. Text read in NFPA first revision 7929, panel 11, A2025 cycle.
- NEC 430.6(A)(2) Separate motor overload protection is based on the nameplate full-load current rating.
- NEC 430.22 Branch-circuit conductors for a single motor, at 125 percent of the table full-load current.
- NEC 430.22(E) Other than continuous duty. Percentage of the NAMEPLATE current, varying by duty classification and by the time rating of the motor. Table 430.22(E).
- NEC 430.24 Conductors supplying several motors or a motor and other loads.
- NEC 430.32 Overload protection for continuous-duty motors, from the nameplate current.
- NEC 430.52 Branch-circuit short-circuit and ground-fault protection. The device has to carry the starting current, and the maximum comes from Table 430.52(C)(1) by motor type and device type.
- NEC 430.52(C)(1) The next higher standard rating is permitted where the table value does not correspond to a standard rating in 240.6. In the 2026 text this permission sits at 430.52(C)(1)(a).
- NEC 430.62 Feeder short-circuit and ground-fault protection. 430.62(A) is a maximum, so the next-higher permission from the branch-circuit rule does not apply here.
- NEC 240.4(B) The general next-higher-standard-rating rule, with its three conditions and its 800 ampere cap.
- NEC 240.6(A) Standard ampere ratings, for every rounding step above.